44

Installation, Operation & Maintenance

HTV/HTD/HTH SERIES

Heat Controller, Inc.

See “ Does

not Operate

in Clg”

See “ Only

Comp

Runs”

Start

Did Unit

Attempt to

Start?

Did Unit

Lockout at

Start-up?

Unit Short

Cycles?

Only Fan

Runs?

Only

Compressor

Runs?

Did unit lockout

after a period of

operation?

Does unit

operate in

cooling?

Unit is OK!

‘See Performance

Troubleshooting’ for

further help

Check Main

power (see power

problems)

Check fault LED code

on control board

Yes

No

No

No

No

No

Yes

No

Yes

See HP

Fault

See

LP/LOC

Fault

See FP1

Fault

See FP2

Fault

See

Condensate

Fault

See Over/

Under

Voltage

No fault

shown

Replace

CXM

See “ Unit

short

cycles”

See “ Only

Fan Runs”

No

Yes

Yes

Yes

Yes

CXM Functional

Troubleshooting Flow Chart

CXM Process Flow Chart

WARNING!

WARNING!

HAZARDOUS VOLTAGE! DISCONNECT

ALL ELECTRIC POWER INCLUDING REMOTE
DISCONNECTS BEFORE SERVICING.
Failure to disconnect power before servicing can cause
severe personal injury or death.