Unit operating conditions, Htv/htd/hth series, Installation, operation & maintenance – Comfort-Aire HTH Series User Manual

Page 34: Heat controller, inc

Advertising
background image

34

Installation, Operation & Maintenance

HTV/HTD/HTH SERIES

Heat Controller, Inc.

Unit Operating Conditions

Table 10: Water Temperature Change Through Heat Exchanger







Antifreeze Type

Antifreeze

%

Cooling

Heating

WPD

Corr. Fct.

EWT 30°F

EWT 90°F

EWT 30°F

Total Cap

Sens Cap

Power

Htg Cap

Power

Water

0

1.000

1.000

1.000

1.000

1.000

1.000

Propylene Glycol

5

0.995

0.995

1.003

0.989

0.997

1.070

15

0.986

0.986

1.009

0.968

0.990

1.210

25

0.978

0.978

1.014

0.947

0.983

1.360

Methanol

5

0.997

0.997

1.002

0.989

0.997

1.070

15

0.990

0.990

1.007

0.968

0.990

1.160

25

0.982

0.982

1.012

0.949

0.984

1.220

Ethanol

5

0.998

0.998

1.002

0.981

0.994

1.140

15

0.994

0.994

1.005

0.944

0.983

1.300

25

0.986

0.986

1.009

0.917

0.974

1.360

Ethylene Glycol

5

0.998

0.998

1.002

0.993

0.998

1.040

15

0.994

0.994

1.004

0.980

0.994

1.120

25

0.988

0.988

1.008

0.966

0.990

1.200

Antifreeze Correction Table

Table 9a: HT Coax Water Pressure Drop

Model

GPM

Pressure Drop (psi)

30°F

50°F

70°F

90°F

026

2.3
3.0
3.4
4.5
6.0

0.7
1.1
1.3
2.0
3.1

0.4
0.7
0.9
1.4
2.3

0.4
0.6
0.8
1.2
1.9

0.5
0.7
0.8
1.2
1.8

038

3.0
4.5
6.0
6.8
9.0

1.5
2.6
3.8
4.5
6.9

0.9
1.7
2.7
3.2
5.2

0.8
1.5
2.3
2.7
4.4

0.9
1.5
2.2
2.6
4.1

049

4.5
6.0
6.8
9.0

12.0

1.5
2.6
3.8
4.5
6.9

0.6
1.1
1.4
2.5
4.2

0.5
1.0
1.3
2.3
3.8

0.3
0.9
1.2
2.2
3.5

064

6.0
7.5
9.0

11.3
12.0
15.0

0.9
1.7
2.5
3.7
4.1
6.1

0.2
0.9
1.5
2.6
3.0
4.7

0.2
0.7
1.3
2.3
2.6
4.1

0.3
0.8
1.4
2.3
2.6
4.0

072

7.0
8.5

10.5
12.8
14.0
17.0

1.4
2.2
3.3
4.6
5.4
7.6

0.7
1.3
2.2
3.4
4.1
6.0

0.5
1.1
1.9
3.0
3.6
5.4

0.7
1.2
2.0
2.9
3.5
5.2

024

036

048

060

070