.2 Connection procedure

Proceed as follows:

1

Unscrew the housing cover

2

If an indicating and adjustment module is installed, remove it by
turning it slightly to the left.

3

Loosen compression nut of the cable entry

4

Remove approx. 10 cm (4 in) of the cable mantle, strip approx.
1 cm (0.4 in) of insulation from the ends of the individual wires

5

Insert the cable into the sensor through the cable entry

6

Lift the opening levers of the terminals with a screwdriver (see
following illustration)

7

Insert the wire ends into the open terminals according to the wiring
plan

Fig. 7: Connection steps 6 and 7

8

Press down the opening levers of the terminals, you will hear the
terminal spring closing

9

Check the hold of the wires in the terminals by lightly pulling on
them

10 Connect the screen to the internal ground terminal, connect the

outer ground terminal to potential equalisation

11 Tighten the compression nut of the cable entry. The seal ring must

completely encircle the cable