Faults

Causes

Measures

No output signal

Cable break

Check the continuity

Deviating zero point signal

Overpressure limit exceeded

Observe the permissible overpressure safety

(see chapter "3. Specifications")

Deviating zero point signal

Operating temperature too high/low

Observe the permissible temperatures

(see chapter 3. "Specifications")

Constant output signal upon

change in pressure

Mechanical overload caused by

overpressure

Replace pressure transmitter; if it fails

repeatedly, contact the manufacturer

Signal span too small

Mechanical overload caused by

overpressure

Replace pressure transmitter; if it fails

repeatedly, contact the manufacturer

Signal span varies

EMC interference sources in the

environment; for example, frequency

converter

Shield the pressure transmitter; cable shield;

remove source of interference

Signal span varies/inaccurate

Operating temperature too high/low

Observe the permissible temperatures

(see chapter 3. “Specifications”)

Signal span drops/too small

Signal span drops/too small

Contact manufacturer and replace pressure

transmitter

If complaint is unjustified, we will charge you the complaint processing fees.

CAUTION!

If faults cannot be eliminated by means of the measures listed above, shut down the

instrument immediately, and ensure that pressure and/or signal are no longer present, and

secure the instrument from being put back into operation inadvertently. In this case, contact

the manufacturer. If a return is needed, please follow the instructions given in chapter 9.2

"Return".

8. Faults

8. Faults

In the event of any faults, first check whether the pressure transmitter is mounted correctly, mechani-

cally and electrically.