WIKA safety manual temperature transmitter T32.xS

Application (see table page 11):

Example 1

Sensor type Pt100, configured measuring range = -50 … +100 °C, so configured

measuring span = 150 K.

This is not smaller than 84 K. Thus the Total Safety Accuracy is 2 % FS,

thus 2 % * 150 K = 3 K,

and/or 2 % * 16 mA = 320 μA in terms of the current output

Example 2

Sensor type Pt100, configured measuring range = 0 … 50 °C, so configured

measuring span = 50 K

This is smaller than 84 K, thus the total safety accuracy is 2 K,

thus 2 K / 50 K = 4 %, and 4 % * 16 mA = 640 μA in terms of the current output

2.7 Configuration changes

WARNING!

During the configuration change, the safety function is not active! Safe

operation is only admissible with activated write protection (password).

Carry out configuration changes within the permissible specifications in accordance

with chapter "2.1 Intended use in safety applications".

With the supplied configuration tools, the write protection, and other items, for the

model T32.xS is settable:

WIKA T32 Configuration Software

AMS

SIMATIC PDM

DTM (from Version DTM Beta version V1.0.2, January 2003) in conjunction with

operating software to the FDT/DTM Standard, e.g. PACTware, FieldMate

HART

®

hand-held terminal FC475, FC375, MFC4150

WARNING!

The safety function must be checked following any configuration

procedure.