WIKA safety manual temperature transmitter T32.xS

11583631.02 11/2010 GB/D/F/E

3.1 FMEDA Pt100 3-wire (safety function for 4 … 20 mA output)

2)

λ

du

30 FIT

1)

λ

dd

2037 FIT

1)

λ

su

sd

118 FIT

1)

SFF – Safe Failure Fraction

98.6 %

MTTR

8 h

PFD for T

proof

1 year

1.316 x 10

-4

DC proof-test-coverage

incl. signal conditioning chain

99 %

3.2 FMEDA Pt100 4-wire (safety function for 4 … 20 mA output)

λ

du

34 FIT

1)

λ

dd

2037 FIT

1)

λ

su

sd

119 FIT

1)

SFF – Safe Failure Fraction

98.6 %

MTTR

8 h

PFD for T

proof

1 year

1.482 x 10

-4

DC proof-test-coverage

incl. signal conditioning chain

99 %

3.3 FMEDA Pt100 2-wire (safety function for 4 … 20 mA output)

λ

du

414 FIT

1)

λ

dd

1657 FIT

1)

λ

su

sd

118 FIT

1)

SFF – Safe Failure Fraction

81.2 %

MTTR

8 h

PFD for T

proof

1 year

1.815 x 10

-3

DC proof-test-coverage

incl. signal conditioning chain

99 %

3.4 FMEDA

thermocouple with internal cold junction

(safety function for 4 … 20 mA output)

λ

du

265 FIT

1)

λ

dd

4807 FIT

1)

λ

su

sd

116 FIT

1)

SFF – Safe Failure Fraction

94.9 %

MTTR

8 h

PFD for T

proof

1 year

1.162 x 10

-3

DC proof-test-coverage

incl. signal conditioning chain

99 %

1) FIT = Failure in time, Unit: Quantity of failures per 10

9

h

2) Determine the distribution of error patterns in WIKA TRxx Sensors

Page 2/3

Appendix 1: SIL Declaration of Conformity

SIL Declaration of Conformity

Functional safety per DIN EN 61508 / DIN EN 61511