6. Commissioning, operation

WARNING!

Never connect directly to a voltage supply (e.g. 24 V) as

this will damage the display.

Only use a transmitter that will not exceed the

permissible electrical limit values.

6.1 Operating a current loop

Power

supply

unit

DC 24 V

internal

bridge

DIH10

display

Housing

WARNING!

The display is only ever operated in a 4 ... 20 mA current

loop. A direct connection to a voltage supply (e.g. DC 24 V)

will lead to the display being damaged and will invalidate

the warranty.

For a functional check, the display must be powered from a

mA source (e.g. mA transmitter or calibrator).

In normal operation, the display is connected in series with

a 4 ... 20 mA transmitter or connected to the 4 ... 20 mA

analogue output of an instrument.