6.3 Programming the display
6.3.1 Programming table for programming the display

PN Description

Range

Factory

default *

0

Calibration mode

0 = Sensor calibration (signal must be

applied, only for factory setting)

1 = Rescaling (display value at 4 ... 20 mA)

0/1

1

1

Full scale value (programming the display

value at 20 mA, e.g. 600)

-999...9999 150

2

Initial value (programming the display value

at 4 mA, e.g. 100)

-999...9999 0

3

Decimal point or unit selection

(for programming a unit, the value shifts to

the left)

0 / 0.0 / 0.00

/ 0.000 /

°F / °C

°C

4

Display and averaging time in 1/10 of a second 5.0 ... 100.0 10

5 **

Zero point stabilisation (the ± range in which

0000 will be displayed)

0 ... 100

2

50 *** Definition of PIN code > 0000 (for

programming lock)

0000...9999 0000

51 *** Authentication by PIN code (removal of

programming lock)

0000...9999 0000

100

Number of reference points (reference points

for sensor calibration, reference points

reduce the measuring rate)

0 ... 30

0

101 ...

130

Reference points (as programmed under

PN100)

-999 ... 9999 0

200

TAG number

0000 ... 9999 0

* For factory setting

** For programming a value >1 a hysteresis of 0.1 % will be activated. This prevents

the display jumping.

*** optional

(If no PIN code has been defined, PN50/PN51 are not available. A PIN code can

only be initially programmed via the serial interface for the factory programming. If a

PIN code has been defined (display after segment test: Pin), the programming lock

must be released, using the PIN code defined via PN50, through PN51 under input,

as otherwise, any changes made under the other PN's will not be able to be saved.

In order to reactivate the PIN code via PN50 on completion of any programming,

the programming mode must be left (by the input of 0000 under PN50 or by briefly

interrupting the current loop).