An362 – Cirrus Logic AN362 User Manual
Page 9

AN362
AN362REV1
9
4.2Accuracy Results for Reactive Energy Load Performance
Figure 8. Reactive Energy Load Performance vs IEC 62053-23 Class 2 Standard
Power Factor
Load Current (A)
Current Dynamic Range (x:1)
Error
sin
= 1
100
1
-0.05%
10
10
-0.03%
1
100
-0.01%
0.2
500
-0.03%
0.1
1000
-0.02%
0.05
2000
-0.06%
0.03
3333
-0.06%
0.025
4000
-0.07%
Lagging sin
= 0.5
100
1
0.28%
10
10
0.16%
1
100
0.11%
0.2
500
0.09%
0.1
1000
0.06%
0.05
2000
-0.08%
Leading sin
= 0.5
100
1
-0.29%
10
10
-0.21%
1
100
-0.15%
0.2
500
-0.16%
0.1
1000
-0.16%
0.05
2000
-0.32%
Table 5. Reactive Energy Load Performance
-3
-2
-1
0
1
2
3
0.01
0.1
1
10
100
Pe
rc
e
n
t Er
ror (
%
)
Load Current (A)
sin
ࢥ = 1
Lagging sin
ࢥ = 0.5
Leading sin
ࢥ = 0.5
Note: CS5480, where U
n
= 240
V, max = 2.5
(100
A) at 50
Hz
IEC 62053-23 Class 2 Spec, sin
ࢥ = 0.5
IEC 62053-23 Class 2 Spec, sin
ࢥ = 1