Single-Phase Pad-Mounted Compartmental-Type Distribution Transformers

An optional trip indicator is available, consisting of

an indicator lens which appears orange when the

interrupter is in the TRIPPED position.

Some Magnex Interrupters are supplied with an

optional emergency overload setting. The emergency

overload will allow approximately 30% overload be-

fore tripping. Using a live-line tool (hot stick), operate

the emergency overload as follows.

− To enable emergency overload, rotate

the handle upward in a counterclockwise

direction, until the handle is in the OPEN

position. Next, turn the emergency over-

load lever counterclockwise to the EO po-

sition. Then rotate the handle downward

in a clockwise direction, until the handle

is in the CLOSED position.

− To disable emergency overload, rotate

the handle upward in a counterclockwise

direction, until the handle is in the OPEN

position. Next, turn the emergency over-

load lever clockwise to the NORMAL posi-

tion. Then rotate the handle downward in

a clockwise direction, until the handle is

in the CLOSED position.

The Magnex Interrupter does not provide a visible

disconnect and should not be relied on as the sole

indication that the transformer secondary terminals

are de-energized.

!

WARNING

FAILURE TO FOLLOW THE INSTRUCTIONS

BELOW COULD RESULT IN DEATH OR SERIOUS

PERSONAL INJURY, AND COULD ALSO RESULT

IN DAMAGE TO THE EQUIPMENT.

• Do not rely solely on the Magnex interrupter

to de-energize the transformer secondary. Al-

ways ground the secondary terminals before

performing work.

• Operate the Magnex Interrupter with a live-

line tool (hot stick or shotgun stick). Never

operate by hand.

• Do not operate the Magnex Interrupter if

there is evidence of tank distress or leaking.

• The handle must be rotated fully against the

stop in the CLOSED position.

Other Switching and Fusing Devices

Transformers may be provided with switching and

fusing devices not discussed in these instructions. In

such cases contact the Howard Industries Transform-

er Division or the device manufacturer for instruc-

tions.