Single-Phase Pad-Mounted Compartmental-Type Distribution Transformers

Table 4: Torque Guidelines for Accessories

Component

Nominal

Torque

(in-lbs)

Torque

Range

Bay-O-Net fuse cartridge

end plug

70

60-80

Bay-O-Net fuse holder-to-

cartridge connection

70

60-80

Bushing-mounted weak-

link fuse mounting bolts

150

140-160

Dry-well fuse canister

clamp

60

40-80

Fluid-level sight plug

600

480-720

Fill plug

960

900-1020

Drain plug

960

900-1020

Drain valve

600

480-720

Automatic pressure relief

valve, 1/4” NPT

180

160-200

Automatic pressure relief

valve, 1/2” NPT

180

170-190

Neutral strap fastener (at

ground pad)

160

140-180

Series/multiple, delta/wye

or tap switch mounting nut

120

96-144

MOV arrester disconnector

nut (ECI brand)

120

96-144

Ground connector

160

140-180

Rotary load-break switch

mount (Central Moloney

brand)

1200

1100-

1300

Rotary load-break switch

mount (Cooper Power

brand)

600

480-720

Rotary load-break switch

handle, Allen screw

55

45-65

When checking tightness of gasketed components, the measured

torque will normally be less than the nominal torque listed in the table

above due to relaxation of the gasket material. Additional tightening of

bushing mounting hardware may cause the component to crack or the

gasket to become over-compressed.

Additional Maintenance Instructions

Features and accessory devices discussed herein

may not be present in all transformers. Some fea-

tures or accessory devices may be present on a

transformer, but not discussed in these instructions.

Howard Industries does not represent that these

instructions are complete, sufficient, accurate or use-

ful for all circumstances.

Questions regarding installation, operation, and

maintenance should be directed to the Howard

Industries Transformer Division, particularly when

encountering unusual or special circumstances not

sufficiently covered by these instructions.

Repair Parts

Repair parts can be ordered from the Howard Indus-

tries Transformer Division. A description of the part

and the transformer serial number will be required to

ensure that the correct part has been ordered.

Warranty Claims

The Howard Industries Transformer Division should

be notified immediately when problems are discov-

ered during the warranty period. All warranty repairs

must be made or approved by the Howard Industries

Transformer Division.