Classic Circular 36"/54" Washfountain with Foot Control
WF2605, WF2608 Terrazzo — WF2705, WF2708 Stainless Steel

Installation Instructions

Bradley Corporation • 215-603 Rev. M; EN 06-915B

6

4/6/2007

Rough-In Specifications

... Continued

Rough-In Notes:
1. All pipes and fittings not furnished by Bradley are shown in broken lines.
2. Supply lines for one to two washfountains should be 1"; for three washfountains 1-1/4"; for more
than three washfountains, pipe sizes should be increased proportionately.
3. Overhead supplies must be reduced to 1/2" copper tube to pass through support tube.
4. Check valve inlets are 1/2" NPT.
5. Dimensions shown in parentheses are millimeters.

Type H

Centrally rising vent with

supplies from below

36" (914) bowl

54" (1372) bowl

36" (914) bowl

54" (1372) bowl

Type O

Off-line vent with

supplies from above

1" NPT supplies through
floor: stub up 2-1/2" (64)

above floor

1" NPT supplies from above

must reduce to 1/2 nom. copper

tube on these centers to

pass thru washfountain

2" NPT drain:

stub up 3" (76)

above floor

7-5/8"

(194)

7-5/8"

(194)

7/8"

(22.2)

7/8"

(22.2)

4"

(102)

4"

(102)

1-1/2" NPT

vent to

ceiling

2" NPT drain:

stub up 3" (76)

above floor

Hot

Hot

Cold

1-1/4"

(32)

Cold

2-1/2"

(64)

TOP VIEW

TOP VIEW

NOTE: UPC and IPC restrict the vertical
distance from the fixture outlet to the trap
weir to not more than 24". Check state and
local codes for variances.