Bryant 3-PHASE 602A User Manual

Page 14

Advertising
background image

leads are inside the unit, run leads up the high-voltage raceway to
the line wiring splice box (See Fig. 12–17). On all 3-phase units,
connect the leads to the black, yellow, and blue wires (See Fig.
16).

C.

CONNECTING GROUND LEAD TO GROUND LUG

Connect the ground lead to the chassis using the ground lug in the
wiring splice box (See Fig. 16).

D.

ROUTING CONTROL POWER WIRES (24-V)

Form a drip-loop with the thermostat leads before routing them
into the unit. Route the thermostat leads through grommeted,
low-voltage hole provided in unit into unit control power splice
box (See Fig. 2 and 3). Connect thermostat leads to unit control
power leads as shown in Fig. 15.

The unit transformer supplies 24-v power for complete system
including accessory electrical heater. An automatic-reset circuit
breaker (See Fig. 17) is provided in the 24-v circuit; see the caution
label on the transformer or Fig. 18. Transformer is factory wired
for 230-v operation. If supply voltage is 208-v, rewire transformer
primary as described in Special Procedures for 208-v Operation
section.

E.

SPECIAL PROCEDURES FOR 208-V OPERATION

1. Disconnect the yellow primary lead from the transformer.

See unit wiring label (See Fig. 12).

2. Connect the yellow primary lead to the transformer terminal

labeled 200-v.

Indoor blower-motor speeds may need to be changed for 208-v
operation. Refer to indoor airflow and airflow adjustments section.

Fig. 15—Control Connections

C99056

Y

C

W2

E

G

R

O

THERMOSTAT

AND SUBBASE

UNIT CONTROL POWER

SPLICE BOX

BRN

WHT

YEL

GRN

RED

ORN

Fig. 16—Line Power Connections

C99057

GROUND LUG

(IN SLPICE BOX)

BLU

YEL

BLK

GROUND

LEAD

SINGLE-PHASE
CONNECTIONS
TO DISCONNECT
PER NEC

3-PHASE
CONNECTIONS

LEGEND
NEC – National Electrical Code

Field Wiring
Splice Connections

NOTE: Use copper wire only.

L1

L3

L2

Fig. 17—Control Wiring Plate

C99070

24 V Circuit Breaker

24 Volt Compartment

Fig. 18—Transformer Label

C99058

TRANSFORMER CONTAINS A MANUAL
RESET OVERCURRENT PROTECTOR

IT WILL NOT AUTOMATICALLY RESET

DISCONNECT POWER AND INSTALL
LOCKOUT TAG PRIOR TO SERVICING

THIS COMPARTMENT MUST BE CLOSED
EXCEPT WHEN SERVICING