Bryant 3-PHASE 602A User Manual

Page 9

Advertising
background image

VII.

INSTALL ELECTRICAL CONNECTIONS

WARNING: The unit cabinet must have an uninter-
rupted, unbroken electrical ground to minimize the pos-
sibility of personal injury if an electrical fault should
occur. This ground may consist of an electrical wire
connected to the unit ground lug in the control compart-
ment, or conduit approved for electrical ground when
installed in accordance with NEC, ANSI/NFPA Ameri-
can National Standards Institute/National Fire Protection
Association (latest edition) (in Canada, Canadian Electri-
cal Code CSA C22.1) and local electrical codes. Failure
to adhere to this warning could result in serious injury or
death.

CAUTION: Failure to follow these precautions could
result in damage to the unit being installed:
1. Make all electrical connections in accordance with

NEC ANSI/NFPA (latest edition) and local electrical
codes governing such wiring. In Canada, all electrical
connections must be in accordance with CSA standard
C22.1 Canadian Electrical Code Part 1 and applicable
local codes. Refer to unit wiring diagram.

2. Use only copper conductor for connections between

field-supplied electrical disconnect switch and unit.
DO NOT USE ALUMINUM WIRE.

3. Be sure that high-voltage power to unit is within

operating voltage range indicated on unit rating plate.
On 3-phase units, ensure phases are balanced within 2
percent. Consult local power company for correction
of improper voltage and/or phase imbalance.

4. Insulate low-voltage wires for highest voltage con-

tained within conduit when low-voltage control wires
are in same conduit as high-voltage wires.

5. Do not damage internal components when drilling

through any panel to mount electrical hardware, con-
duit, etc.

A.

HIGH-VOLTAGE CONNECTIONS

The unit must have a separate electrical service with a field-
supplied, waterproof disconnect switch mounted at, or within sight
from the unit. Refer to the unit rating plate, NEC and local codes
for maximum fuse/circuit breaker size and minimum circuit amps
(ampacity) for wire sizing (See Tables 5 and 6 for electrical data).

The field-supplied disconnect may be mounted on the unit over the
high-voltage inlet hole (See Fig. 2 and 3).

If the unit has an electric heater, a second disconnect may be
required. Consult the Installation, Start-Up, and Service Instruc-
tions provided with the accessory for electrical service connec-
tions.

Operation of unit on improper line voltage constitutes abuse and
may cause unit damage that could affect warranty.

B.

ROUTING POWER LEADS INTO UNIT

Use only copper wire between disconnect and unit. The high-
voltage leads should be in a conduit until they enter the duct panel;
conduit termination at the duct panel must be watertight. Run the
high-voltage leads through the power entry knockout on the power
entry side panel. See Fig. 2 and 3 for location and size. When the

TABLE 4—MINIMUM AIRFLOW FOR RELIABLE ELECTRIC HEATER OPERATION (CFM)

SIZE

602A030

602A036

602A042

602A048

602A060

AIRFLOW (CFM)

1000*

1200

1400

1600

2000

* The 030 size models must be run on medium or high speed when used in conjunction with 15 kw electric heat accessory

Fig. 9—Typical Installation

C00139

INDOOR
THERMOSTAT

DISCONNECT
PER NEC

FROM
POWER
SOURCE

RETURN
AIR

TOP COVER

Fig. 10—602A with Duct Covers On

(Unit Shown with Optional Louvered Grille)

C99030

Horizontal Duct Covers

Fig. 11—Condensate Trap

C99013

1” (25mm) MIN.

2” (50mm) MIN.

TRAP
OUTLET

—9—

Advertising
This manual is related to the following products: