Model 91 bay minimum clearances, Floor protection, Tools for installation – New Buck Corporation 91 User Manual

Page 14

Advertising
background image

MODEL 91 BAY

MINIMUM CLEARANCES


The New Buck Corporation Model 91 Bay
must be installed in compliance with the instructions contained in
this manual.

Clearance from combustible walls and ceilings. (Using single wall chimney connector)


The minimum lateral distance between any part of the room heater and combustible walls is shown in Figures 1
and 2.















FLOOR PROTECTION


If a freestanding model is to be installed on a combustible floor, a non-combustible pad must be placed below it to
protect the floor from burning material from the stove. The pad must be 50 inches wide. NOTE: The floor must
extend 16" from door opening in front of the stove, 8" from the door opening on each side, and should be under
the chimney connector. Floor protector must by 3/8" in minimum thickness, non-combustible material or
equivalent.

The unit must be positioned on the pad so that there is a minimum of 16" from the front of the door opening to the
front of the pad, and a minimum of 8" measured horizontally from the sides of the fuel loading and ash removal
openings to the sides of the pad.

NOTE: For clearance reductions using wall protectors, refer to the NFPA-211 Code.

TOOLS FOR INSTALLATION


Drop Cloth
Electric Drill with 7/32" drill bit
1/2" - 9/16" combination wrench
3/8" magnetic socket chuck adapter, 3/8" wrench (box or socket) or adjustable wrench
Socket Set
Tape Measure
Pencil
Level
Screw Driver