5/21/08 Bradley

Corporation • 215-1628 Rev. A; EN 08-201

D - Setting Scrub Mode (60 seconds)

Setting scrub mode for 60 seconds will allow the faucet to activate for 60
seconds from the last hand presence.

1 Enable

“Manual

Setting”

Mode

> see “Enabling Manual Setting Mode” section

2 Fully cover sensor with hand. Water fl ow stops after 5 seconds - Continue to

hold on for another three (3) additional water pulses.

3 Remove hand.

Result: Scrub Mode is now activated for 60 seconds.

E - Setting Scrub Mode (180 seconds)

Setting scrub mode for 180 seconds will allow the faucet to activate for 180
seconds from the last hand presence.

1 Enable

“Manual

Setting”

Mode

> See “Enabling Manual Setting Mode” section

2 Fully cover sensor with hand. Water fl ow stops after 5 seconds - Continue to

hold on for another four (4) additional water pulses.

3 Remove hand.

Result: Scrub Mode is now activated for 180 seconds.

F - Sensor Range Adjustment

The detection distance of the sensor can be adjusted between approximately

4 - 11 inches from the infrared window.

1 Enable

“Manual

Setting”

Mode

> See “Enabling Manual Setting Mode” section

2 Remove all items from the sink.

2 Fully cover sensor with hand. Water fl ow stops after 5 seconds - Continue to

hold on for fi ve (5) additional water pulses.

4 Remove hand.

5 Hold hand in the current detection area until LED fl ashes. Then move hand

to the desired detection distance. When LED stays lit for two (2) seconds,
detection distance has been re-set to new location.

Result: The detection distance is now calibrated.

G - Reset

All settings will be reset to default setting. The “Manual Setting” Mode will be
disabled.

> The procedure for the reset is the same as “Enabling Manual Setting Mode”,
but step 5 needs to be done six (6) times in a row.

Result: All settings are reset to default settings and the manual-setting-mode is

now disabled.