Outdoor Coil Thermistor

The outdoor coil thermistor is a 10Kohm resistor used for multiple

system operations. It provides the coil/liquid line temperature to
the heat pump board and user interface. Low ambient operation,

defrost initiation, defrost termination and assistance with OAT

temperature measurement of some of the functions. The sensor
must be securely mounted to the tube connecting the EXV and

distributor. See Fig. 15 for proper placement. See Table 4 for
proper resistances.

OAT Thermistor must be

locked in place with

spherical nib end facing

towards the front of the

control box

A11142

Fig. 15 -- OAT Thermistor Location (Bottom of Control Box)

OCT SENSOR

LOCATION

A11143

Fig. 16 -- Outdoor Coil Thermistor (OCT) Attachment

(On Distributor Tube)

REVERSING VALVE

ACCUMULATOR

SUCTION TUBE

SUCTION THERMISTOR (OST)

SUCTION SERVICE VALVE

ACCUMULATOR TUBE

COMPRESSOR

PRESSURE TRANSDUCER (SPT)

A11103

Fig. 17 - Suction Thermistor (OST) Attachment

(On Suction Tube)

Suction Thermistor (OST)

Suction Thermistor is used for assisting in EXV control and must

be secured on the suction tube and aligned longitudinally to the
vertical surface of the tube axis (see Fig. 17).

CAUTION

!

UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment

damage or improper operation.
In order to minimize the ambient influence, make sure the

thermistor curved surface hugs the pipe surface and is

secured tight using the wire tie fished through the original

slot insulating polymer body.

Variable Speed Compressor Sensor Output Terminals

This compressor has a motor thermistor and a scroll thermistor.
Correct resistance between scroll thermistor terminal and common

is 10k at 77_F (25_C).

Correct resistance between motor

thermistor terminal and common is 5k at 77_F (25_C).

Variable Speed Compressor Power Input Terminals

This compressor operates with a 3--phase variable frequency PWM

variable voltage to the three fusite terminals.

Table 5 – Variable Speed Compressor Resistances

(winding resistance at 70_F20_F)

WINDING

280ANV024

280ANV036

280ANV048

280ANV060

Between terminals

T1, T2, and T3

.681

.203

Between terminal &

ground

>1 mega OHM

>1 mega OHM

UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage

and/or improper operation.
Do not use Meggar for measuring the winding resistance.

CAUTION

!

ECM Fan Motor

If verification of proper operation is required for the ECM motor

used in this unit, follow these steps:

1. Verify that the 230v input to the transformer is present.
2. Verify that the control board is powered 18 volts to 30 volts

from the transformer.

3. With the UI in charging mode in cooling, measure the DC

voltage between the PWM 1 and PWM 2 terminals on the

outdoor control board. The DC voltage and PWM (option-
al) measured must be as shown in Table 6.

Table 6 – DC Voltage and PWM Measurement

Unit Size

Voltage

PWM

024, 036

8.9 VDC

52

048, 060

11.1 VDC

84