Step 2 — Install on a Solid, Level Mounting Pad

If conditions or local codes require the unit be attached to pad, tie
down bolts should be used and fastened through knockouts

provided in unit base pan. Refer to unit mounting pattern in Fig. 3

to determine base pan size and knockout hole location.
For hurricane tie downs, contact distributor for details and PE

(Professional Engineer) Certification, if required.
On rooftop applications, mount on level platform or frame. Place

unit above a load--bearing wall and isolate unit and tubing set from
structure. Arrange supporting members to adequately support unit

and minimize transmission of vibration to building. Consult local

codes governing rooftop applications.
Roof mounted units exposed to winds above 5 mph may require

wind baffles. Consult the Service Manual -- Residential Split
System Air Conditioners and Heat Pumps Using Puron®

Refrigerant for wind baffle construction.
NOTE: Unit must be level to within ±2° (±3/8 in./ft,±9.5 mm/m.)
per compressor manufacturer specifications.

Step 3 — Clearance Requirements

When installing, allow sufficient space for airflow clearance,

wiring, refrigerant piping, and service. Allow 24 in. (609.6 mm)
clearance to service end of unit and 48 in. (1219.2 mm) (above

unit. For proper airflow, a 6--in. (152.4 mm) clearance on 1 side of

unit and 12--in. (304.8 mm) on all remaining sides must be
maintained. Maintain a distance of 24 in. (609.6 mm) between

units. Position so water, snow, or ice from roof or eaves cannot fall
directly on unit.
On rooftop applications, locate unit at least 6 in. (152.4 mm) above

roof surface.

3/8---in. (9.53 mm) Dia.

Tiedown Knockouts in

Basepan(2) Places

View From Top

A05177

UNIT BASE PAN

Dimension in. (mm)

TIEDOWN KNOCKOUT LOCATIONS in. (mm)

A

B

C

35 X 35

(889 X 889)

9–1/8 (231.8)

6–9/16 (166.7)

28–7/16 (722.3)

Fig. 3 -- Tiedown Knockout Locations

Step 4 — Operating Ambient

The minimum outdoor operating ambient in cooling mode is 55_F

(12.78_C) without low ambient cooling enabled, and the

maximum outdoor operating ambient in cooling mode is 125_F
(51.67_C). The maximum heating operation ambient is 66_F

(18.9_C). Compressor protections prevent operation below --10 to
--20_F.

Step 5 — Elevate Unit

Elevate unit per local climate and code requirements to provide
clearance above estimated snowfall level and ensure adequate

drainage of unit.

CAUTION

!

UNIT OPERATION HAZARD
Failure to follow this caution may result in equipment

damage or improper operation.
Do not allow water and/or ice to build up in base pan.

CAUTION

!

UNIT OPERATION HAZARD
Failure to follow this caution may result in equipment

damage or improper operation.
Locate the unit in such a way that it is stable in all

circumstances including adverse weather conditions.

Step 6 — In Long--Line Applications, Install

Liquid--Line Solenoid Valve (LSV)

For refrigerant piping arrangements with equivalent lengths of
greater than 80 ft. (24.38 m) and/or when elevation difference

between indoor and outdoor unit is greater than ±20 ft. (±6.10 m),

follow the piping configuration and liquid line solenoid valve

(LSV) accessory requirements from the Residential Piping and

Long--line guideline. CCH, start gear and piston changes do not
apply. If required by Long--Line Guideline, install LSV kit, part

no. KHALS0401LLS, specifically designed for Puron® refrigerant

heat pumps. LSV should be installed within 2 ft. (0.61 m) of

outdoor unit with flow arrow pointing toward outdoor unit.
Make the necessary electrical connections as shown on Fig. 21 and
by following the Installation Instructions included with accessory

kit.
IMPORTANT: Flow arrow must point toward outdoor unit.

Green

Yellow

White

ABCD
Connection (optional)

Red

LLS

LS

User Interface

Optional Remote

Room Sensor

Furnace or
Fan Coil

Variable
Speed
HP

A

B

C

C

S2

A

B

C

D

A

B

C

D

S1

No

Use

A12053

Fig. 4 -- Liquid Line Solenoid Electrical Connection

(Required for long line applications)