Fig. 7 -- Deep Vacuum Graph

Final Tubing Check

IMPORTANT: Check to be certain factory tubing on both indoor
and outdoor unit has not shifted during shipment. Ensure tubes are
not rubbing against each other or any sheet metal. Pay close
attention to feeder tubes, making sure wire ties on feeder tubes are
secure and tight.

Step 8 — Make Electrical Connections

!

WARNING

ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal

injury or death.
Do not supply power to unit with compressor terminal box

cover removed.

Be sure field wiring complies with local and national fire, safety,

and electrical codes, and voltage to system is within limits shown

on unit rating plate. Contact local power company for correction of
improper voltage. See unit rating plate for recommended circuit

protection device.
NOTE: Operation of unit on improper line voltage constitutes
abuse and could affect unit reliability. See unit rating plate. Do not
install unit in system where voltage may fluctuate above or below
permissible limits.
NOTE: Use copper wire only between disconnect switch and unit.
NOTE: Install branch circuit disconnect of adequate size per NEC
to handle unit starting current. Locate disconnect within sight from
and readily accessible from unit, per Section 440--14 of NEC.

Route Ground and Power Wires

Remove access panel to gain access to unit wiring. Extend wires

from disconnect through power wiring hole provided and into unit
control box.

!

WARNING

ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury

or death.
The unit cabinet must have an uninterrupted or unbroken

ground to minimize personal injury if an electrical fault

should occur. The ground may consist of electrical wire or

metal conduit when installed in accordance with existing

electrical codes.

Connect Ground and Power Wires

Connect ground wire to ground connection in control box for

safety. Connect power wiring to contactor as shown in Fig. 8.

DISCONNECT

PER N. E. C. AND/OR

LOCAL CODES

CONTACTOR

GROUND

LUG

FIELD GROUND

WIRING

FIELD POWER

WIRING

A91056

Fig. 8 -- Line Power Connections

Connect Control Wiring

Connect to Evolution connections.

Only two wires (AB) to

Evolution capable indoor unit (furnace or fan coil) is required.
Typical 4 wire (ABCD) may be connected (see Fig. 18).
IMPORTANT: This system requires the power supply to the
outdoor unit, and the indoor unit, for the UI to communicate with
the outdoor unit.

General Information

Use No. 18 AWG or larger color--coded, insulated (35°C

minimum) wire for low voltage control wires.
All wiring must be NEC Class 1 and must be separated from

incoming power leads.
Use furnace transformer, fan coil transformer, or accessory

transformer for control power requirement of system accessories

external to the OD unit. The outdoor unit has its own transformer
power.

Final Wiring Check

IMPORTANT: Check factory wiring and field wire connections to
ensure terminations are secured properly. Check wire routing to
ensure wires are not in contact with tubing, sheet metal, etc.

Step 9 — Compressor Crankcase Heater

This compressor has an internal crankcase heater. Furnish power

to the unit a minimum of 24 hr before starting the unit for the first
time.
To furnish power to heater only, set thermostat to OFF and close
electrical disconnect to outdoor unit.
Power is not required to the indoor unit or User Interface for proper
operation of heater. Crankcase heater will however be intelligently

energized as needed between operations, and otherwise even when

the UI and indoor unit is not installed, as long as there is power to
the outdoor unit even if the indoor unit and UI are not yet installed.

Airflow Setup for Evolution Control Furnace or

FE Fan Coil (communicating)

This system can only be installed with Evolution indoor and user
interface (UI) SYSTXBBUID01--D or SYSTXBBUIZ01--D

(software version 23 or newer). When using an Evolution User

Interface, airflow is automatically selected based on equipment
size. The user has the option of selecting Comfort, Efficiency and

Max airflow for Heating and/or Cooling modes. These should be
selected based on balance between the homeowner’s comfort and

energy consumption expectations. See User Interface Installation

Instructions for additional available adjustments.
Due to using a communicating control with the fan coil or the

furnace, dip switch adjustments are not necessary. The outdoor
unit configuration and the indoor airflows are determined by

communicating control setup.