Table 7 – Troubleshooting

FAULT DESCRIPTION SENT TO UI

FLASH CODE

(AMBER LED)

RESET TIME

(minutes)

--- ---

Standby

ON, no flash

--- ---

Variable Capacity or Emergency

Mode

1, pause

--- ---

Variable Speed Range Cutback

1 (2 sec ON), longer pause (1

second OFF)

Communications Loss

16

NA

Invalid Model

25

NA

High Pressure Switch Open

31

15

Low Pressure Trip

32

15

Control Fault

45

NA

Brownout

46

Revert to 5 min cycle delay

Lost Inverter Communications

48

Revert to 5 min cycle delay

230VAC Dropout---Reset Event

49

Revert to 5 min cycle delay

Outdoor Air Temp Sensor Fault

53

NA

Suction Temp Sensor Fault

54

15

Coil Temp Sensor Fault

55

NA

OAT---OCT Thermistor Out of range

56

NA

Suction Pressure Sensor Fault

57

15

OAT---OST Thermistor Out of range

58

5

Compressor Scroll Temp Out of Range

59

15

Compressor Sump Heating Active

68

2 HOURS

Inverter / Compressor Internal Fault

69

15

Compressor Motor Temp Out of Range

71

15

Suction Over Temperature

72

15

Inverter Temp Out of Range Event

75

15

Inverter Over Current

77

15

Compressor No---Pump Event

79

15

Suction Over Temp Lockout

82

4 Hours

Low Pressure Lockout for 4 hours

83

4 HOURS

High Pressure Lockout for 4 hours

84

4 HOURS

Compressor Temp Lockout

85

4 HOURS

Compressor Temp Sensor Fault

86

15

Inverter Temp Lockout

88

4 HOURS

Inverter VDC---Out Over Voltage

91

15

Inverter VDC---Out Under Voltage

92

15

230VAC Under Voltage

93

15

230VAC Over Voltage

94

15

High Current Lockout

95

2 HOURS

VDC Under Voltage Lockout

96

2 HOURS

VDC Over Voltage Lockout

97

2 HOURS

High Torque Event

98

10

High Torque Lockout

99

2 HOURS

--- ---

OFF

NA