GPM FlowingGPM FlowingGPM FlowingGPM FlowingGPM Flowing

GPM FlowingGPM FlowingGPM FlowingGPM FlowingGPM Flowing

3/4" Booster3/4" Booster3/4" Booster3/4" Booster3/4" Booster

1" Booster

1-1/2" Hose1-1/2" Hose1-1/2" Hose1-1/2" Hose1-1/2" Hose

1-3/4" Hose with1-3/4" Hose with1-3/4" Hose with1-3/4" Hose with1-3/4" Hose with 1-1/2" Couplings1-1/2" Couplings1-1/2" Couplings1-1/2" Couplings1-1/2" Couplings

2" Hose with2" Hose with2" Hose with2" Hose with2" Hose with 1-1/2" Couplings1-1/2" Couplings1-1/2" Couplings1-1/2" Couplings1-1/2" Couplings

2-1/2" Hose

3" Hose with 2-1/2" Coupling

s

3" Hose

3-1/2" Hose

4" Hose

5" Hose

HOSE FRICTON LOSS (PSI PER 100 FEET)

NOTE: Add 5 PSI for each story of building and each wye or siamese.

NOTE: Add 5 PSI for each story of building and each wye or siamese.

NOTE: Add 5 PSI for each story of building and each wye or siamese.

NOTE: Add 5 PSI for each story of building and each wye or siamese.

NOTE: Add 5 PSI for each story of building and each wye or siamese.

F

FF

FFriction Loss Calcula

riction Loss Calcula

riction Loss Calcula

riction Loss Calcula

riction Loss Calculations Cour

tions Cour

tions Cour

tions Cour

tions Courtesy IFST

tesy IFST

tesy IFST

tesy IFST

tesy IFSTA.

A.

A.

A.

A.

GPM Flowing

HALE PRODUCTS INC.

A UNIT OF IDEX CORPORATION

10

13.5

3.5

95

14

8

500

20

44

6

125

24

13

750

30

99

14

150

35

18

1000

40

176

24

4

175

47

25

6

1250

50

38

7

200

62

32

8

1500

60

54

9

225

10

1750

70

12

250

13

5

4

2000

80

15

275

15

95

22

300

18

125

38

325

22

8

150

54

350

25

8

500

20

17

750

45

38

1000

80

68