Figure 16 – hi-pot setup – Baldor Series 5 Inverter IP-65 User Manual

Page 11

Advertising
background image

9

B.

The hi-pot tester must have an automatic ramp-up to the test voltage and an automatic
ramp-down to zero voltage.

Note:

If the hi-pot tester does not have automatic ramping, then the hi-pot output must

be manually increased to the test voltage and then manually reduced to zero. This pro-
cedure must be followed for each machine to be tested. A suggested hi-pot tester is
Slaughter Model 2550.

WARNING!

Instantaneously applying the hi-pot voltage will cause irreversible dam-

age to the speed control.

C.

The hi-pot test voltage should be set in accordance to the testing agency standards and
the leakage current should be set as low as possible without causing nuisance trips.

D.

To eliminate motor speed control damage due to auxiliary equipment hi-pot failure, it is
also recommended that all signal inputs be wired together and connected to the AC input
lines as shown.

VI. CONTROL OPERATION

A. Start-Up Procedure

– After the control has been properly setup (jumpers and trimpots

set to desired positions and wiring completed), the startup procedure can begin. If the AC
power has been properly brought to the control, the POWER LED will be illuminated
green once the Power On/Off Switch is set to the “ON” position. The STATUS LED will
indicate control status as described in Section IX, on page 13. To start the control,
momentarily set the Start/Stop Switch to the "START" position. The motor will begin to
accelerate to the set speed.

Note:

If the motor rotates in the incorrect direction, it will be necessary to disconnect the

AC line, reverse any two motor leads, and repeat the startup procedure.

B. Fault Recovery

– The control has four fault states – undervoltage, overvoltage, short cir-

cuit at the motor (phase-to-phase) and I

2

t overload protection. To recover from any fault,

it is necessary to momentarily set the Start/Stop Switch to the "START" position.

If the Start/Stop function has been eliminated by installing a jumper between RUN and
COM terminals, then it will be necessary to either disconnect the AC line until the STA-
TUS LED indicates an undervoltage fault (approximately 20 seconds) or use the
Start/Stop Switch (if installed).

2

1

3

0

AC KILOVOLTS

RETURN

H. V.

(MAIN POWER DISCONNECTED)

TERMINALS TOGETHER

CONNECT ALL SPEED CONTROL

HIGH VOLTAGE DIELECTRIC WITHSTAND TESTER

MOTOR SPEED CONTROL

(HI-POT TESTER)

SIGNAL INPUTS

TERMINALS

L1

L2

FRAME

CHASSIS

CHASSIS

MOTOR

MOTOR WIRES

AC LINE INPUTS

RESET

TEST

TO BOTH

CONNECT HI-POT

AC LINE INPUT

LEAKAGE

0mA

10mA

MAX

ZERO

VOLTAGE

AUXILIARY EQUIPMENT

MACHINE OR EQUIPMENT FRAME

L1

L2

P1

P2

P3

FIGURE 16 – HI-POT SETUP

!