Baldor Series 5 Inverter IP-65 User Manual

Page 13

Advertising
background image

11

more rapid deceleration time, rotate the DECEL trimpot coun-
terclockwise. For longer deceleration time, rotate the DECEL
trimpot clockwise. See Figure 20.

Note:

To provide increased resolution of the ACCEL and

DECEL trimpots, 50% rotation covers 0.3 - 5 seconds.

Application Note:

On applications with high inertial loads,

the deceleration may automatically increase in time. This will
slow down the rate of speed decrease to prevent the bus volt-
age from rising to the overvoltage trip point. This function is
called regeneration protection.

It is recommended that for

very high inertial loads that both the ACCEL and DECEL
trimpots should not be set to less than ten (10) seconds.

E. Slip Compensation (COMP)

– Sets the amount of

Volts/Hz/Amp to maintain set motor speed under varying
loads. The COMP trimpot is factory set for 1.5 Volts/Hz/Amp.
The slip compensation may be adjusted by the COMP trim-
pot as described below. See Figure 21.

1. Wire an ammeter in series with one motor phase.

2. Run the motor and set the unloaded speed to approxi-

mately 50%.

3. Load the motor to the rated motor nameplate current

(Amps AC).

4. Adjust the COMP trimpot so that the loaded RPM is equal

to the unloaded RPM.

5. The motor is now compensated to provide constant

speed under varying loads.

F. Current Limit with I

2

t Shutdown (CL)

– Sets the current

limit (overload), which limits the maximum current to the
motor. The current limit set point is established by the setting
of Jumper J3 and the setting of the CL trimpot. See Figure 22.

2.3

0.8

Shown Factory Set to 1.5 Volts/Hz/Amp

1.5

3

0

Volts/Hz/Amp

FIGURE 21

COMP TRIMPOT RANGE

(Shown Factory Set to 160%)

Percent of Range Setting

80

40

160

200

120

FIGURE 22

CL TRIMPOT RANGE

2.5

12.5

(Shown Factory Set to 1.5 Seconds)

1.5

5

Seconds

0.3

20

FIGURE 20

DECEL TRIMPOT RANGE

110

150

140

130

10

120

160

50

1.0

0.1

SETTING (160%)

FACTORY CL

FIGURE 23 – I

2

t TRIP TIME vs MOTOR CURRENT

NOTES:

1. The CL set point is factory set to 160% of nominal motor current.
2. I

2

t Will not trip below 120% of the CL setting.

MOTOR CURRENT (%)

I

2

t TRIP TIME

(minutes)