12

The CL trimpot is factory set for 160% of Jumper J3 range setting. For a higher current
limit setting, rotate the CL trimpot clockwise. For a lower current limit setting, rotate the
CL trimpot counterclockwise. The current limit also contains I

2

t trip function. The control

will trip according to a predetermined current vs. time function. The trip curve is directly
related to the CL set point and can be changed with the CL trimpot. See Figure 23 on
page 11.

CAUTION!

Adjusting the CL above 160% of the motor rating may cause overheating of

the motor. Do not leave the motor in a locked rotor condition for more than a few sec-
onds since motor damage may occur.

G. Boost (BOOST)

– Sets the amount of boost voltage to the

motor. Jumper J7 is factory set to the "FIX" position, which
provides a predefined amount of boost voltage for 50 Hz and
60 Hz motors. To adjust the amount of boost voltage to the
motor, set Jumper J7 to the "ADJ" position. The amount of
boost voltage may be adjusted by the BOOST trimpot as
described below. See Figure 24.

1. Connect an analog AC ammeter in series with one of the

motor leads.

Note:

Generally, digital or clamp-on ammeters do not

yield accurate readings.

2. Run the motor

unloaded

at approximately 4 Hz (or 120 RPM).

Note:

An unloaded motor with excessive boost will draw more current than a partial-

ly loaded motor.

3. Adjust the BOOST trimpot until the ammeter reading reaches the motor nameplate

rating.

4. Using the Main Speed Potentiometer, slowly adjust the motor speed over a 0 - 15 Hz

(0 - 450 RPM) range. If the motor current exceeds the nameplate rating, lower the
boost setting.

WARNING! TO AVOID MOTOR WINDING OVERHEATING AND FAILURE, DO
NOT OVERBOOST THE MOTOR.

1 Sec On - 1 Sec Off

1 Sec On - 1 Sec Off

Control Mode

Slow Flash

Status LED Information

Flash Rate

Color Sequence

Illumination Duration Seconds

Run

Stand-By

1

Short Circuit

I

2

t Fault

Overload

Slow Flash

Slow Flash

Quick Flash

Steady

Undervoltage

Overvoltage

Recovered Undervoltage

2

Recovered Overvoltage

2

1 Sec Red - 1 Sec Yellow - 0.5 Sec Off -
1 Sec Green - 0.5 Sec Off

Quick Flash

Slow Flash

Quick Flash

Slow Flash

Green

Yellow

Red

Red

Red

Red - Yellow

Red - Yellow

Red - Yellow - Off - Green - Off

Red - Yellow - Off - Green - Off

1 Sec On - 1 Sec Off

0.25 Sec On - 0.25 Sec Off

Constant

0.25 Sec Red - 0.25 Sec Yellow

1 Sec Red - 1 Sec Yellow

0.25 Sec Red - 0.25 Sec Yellow -
0.5 Sec Off - 1 Sec Green - 0.5 Sec Off

Notes:

1. Only if the Forward-Stop-Reverse Switch is installed

2. Only if the control is in Manual Reset Mode (Jumper J4 set to the “MAN” position).

TABLE 5 – CONTROL MODE AND STATUS LED INDICATION

9

23

(Shown Factory Set to 5 Volts)

5

16

Volts

0

35

FIGURE 24

BOOST TRIMPOT RANGE

Stop

Steady

Yellow

Constant