9.75

L2906H, 2906H, 3507H, 619A, 723A, 29.6LP, 29.6, 35.7

Electrical System

LEFT STABILIZER
UP VALVE – SHORT
TO GROUND

33227

1

Deactivate output J2-3 Right

Stabilizer Up Valve.

Deactivate output J2-15 Right

Stabilizer Down Valve.

Deactivate output J2-10 Left

Stabilizer Up Valve.

Deactivate output J2-21 Left

Stabilizer Down Valve.

The stabilizers are configured in the

MACHINE SETUP menu and the

UGM detects a short to ground at

this output.

Power cycled.

RIGHT STABILIZER
DOWN VALVE –
OPEN CIRCUIT

33228

1

Deactivate output J2-15 Right

Stabilizer Down Valve.

Deactivate output J2-21 Left

Stabilizer Down Valve

.

The stabilizers are configured in the

MACHINE SETUP menu and the

UGM detects an open circuit at this

output.

Power cycled.

RIGHT STABILIZER
DOWN VALVE –
SHORT TO
BATTERY

33229

1

Deactivate output J2-3 Right

Stabilizer Up Valve.

Deactivate output J2-15 Right

Stabilizer Down Valve.

Deactivate output J2-10 Left

Stabilizer Up Valve.

Deactivate output J2-21 Left

Stabilizer Down Valve.

Deactivate and inhibit output J1-3

(Frame Leveling and Stabilizers will

be cutout).

The stabilizers are configured in the

MACHINE SETUP menu and the

UGM detects a short to battery at

this output.

Power cycled.

RIGHT STABILIZER
DOWN VALVE –
SHORT TO
GROUND

33230

1

Deactivate output J2-15 Right

Stabilizer Down Valve.

Deactivate output J2-21 Left

Stabilizer Down Valve.

The stabilizers are configured in the

MACHINE SETUP menu and the

UGM detects a short to ground at

this output.

Power cycled.

RIGHT STABILIZER
UP VALVE – OPEN
CIRCUIT

33231

1

Deactivate output J2-3 Right

Stabilizer Up Valve.

Deactivate output J2-15 Right

Stabilizer Down Valve.

Deactivate output J2-10 Left

Stabilizer Up Valve.

Deactivate output J2-21 Left

Stabilizer Down Valve.

The stabilizers are configured in the

MACHINE SETUP menu and the

UGM detects an open circuit at this

output.

Power cycled.

RIGHT STABILIZER
UP VALVE – SHORT
TO BATTERY

33232

1

Deactivate output J2-3 Right

Stabilizer Up Valve.

Deactivate output J2-15 Right

Stabilizer Down Valve.

Deactivate output J2-10 Left

Stabilizer Up Valve.

Deactivate output J2-21 Left

Stabilizer Down Valve.

Deactivate and inhibit output

(Frame Leveling and Stabilizers will

be cutout).

The stabilizers are configured in the

MACHINE SETUP menu and the

UGM detects a short to battery at

this output.

Power cycled.

Message

Fault

Code

Indicators

Other Actions Taken

Trigger for Fault

Latch Until