6 interfaces, 1 interface configuration, 2 24v dc power supply – ADS-TEC OPC6012/6015 User Manual

Page 22

Advertising
background image

OPC6012/6015

21

© ads‐tec GmbH • Raiffeisenstr.14 • 70771 Leinfelden‐Echterdingen

6 Interfaces 

6.1 Interface configuration 

 

Interface 

IRQ 

Adress 

COM1 

3F8h 

 

Pos: 26 /Datentechnik/Schnittstellen/Spannungsversorgung/Spannungsversorgung für VMT60xx-Serie @ 2\mod_1260450284020_6.doc @ 6853 @

6.2 24V DC Power Supply 

The supply voltage is provided via a lead‐through terminal including a screw connection (Phoenix Contact 
COMBICON MC 1,5/4‐STF3.81). (The figure shows the socket inside the device). 
 

Pin‐Number 

Signal‐Name 

 

PE 

0 V DC 

NC 

24V DC 

 

 

Technical Data of the input 

• 

Input voltage: 

 

 

19…29V DC 

• 

Max. Input voltage: 

 

7A(10ms) 

 

 

Note: 

The power supply can be protected with a slow‐blow fuse of up to 4A.

 

 

Note: 

The typical power consumption of this device is indicated in the "Technical details" 
chapter.

 

 

Note: 

If the case is connected with earth potential at the provided PE contact (e.g. by connecting 
the PE contact with the device plug), the electrical insulation is no longer given. This also 
applies if the device is installed by using a metal retainer clip. 

If you want to have the device electrically insulated from the power supply, you 
have to use a method of installation that ensures appropriate insulation.

Advertising