Calibration
MODE
DESCRIPTION
PARAMETERS
7
4 mA Trim
Range = 0-9999
Default = 5000
Mode 7 fine tunes the minimum current sourced on the analog output.
MODE
DESCRIPTION
PARAMETERS
8
20 mA Trim
Range = 0-9999
Default = 5000
Mode 8 fine tunes the maximum current sourced on the analog output.
MODE
DESCRIPTION
PARAMETERS
9
Calibration
Range = 0-1999
Default = 1000
Mode 9 is used to calibrate the sensor for variations in the speed of sound
due to variations in atmospheres. The default of 1000 is used for most
applications. Assume a decimal after the first digit.
MODE
DESCRIPTION
PARAMETERS
10
Distance Offset
Units = Mode 1
Range = -3.00 to 3.00
Default = 0
Mode 10 is used to change the zero point of the sensor.