• Circuit Protection
WARNING!
DO NOT EXCEED CONTACT RATINGS! When an inductive load is
used (e.g. a motor, a coil, or an electromagnetic relay), a back
electromotive force of several hundred volts (energy stored in the
inductance) arises when the contacts are opened. This results in
considerable decrease in contact life. The same result arises even
when a resistive load is used with a high voltage or a large current. The
figures below show circuits for protecting the reed switch(s) from the
back electromotive force.
L
C
R
E
C = I
R = Approx.
10 x I (I + 50/E)
E
Protecting Circuit Using CR
Protecting Circuit Using Varistor
Protecting Circuit Using Diode
2
/10 (uF)
Switch
Code A
Code B
Max. contact capacity
20 VA
50 VA
Max. switching current
0.5A AC
0.5 A AC
Max. Voltage
220 VAC
220 VAC