• Troubleshooting

Problem

Not detecting powders when covered.

Possible Causes

• Powder build density is too small. Bulk density under 0.2 cannot be

detected.

• Power supply not connected.
• Material too fluid.
• Effected by heavy hopper vibration.

Remedies

• Set high sensitivity
• Connect power supply.
• Install sensor in a better location.

Problem

• It keeps detecting powders while the hopper is empty.

Possible Causes

• Heavy deposit on vibration rod.
• Material has dead stock.

Remedies

• Clean vibration rod.
• Install sensor in better location or isolate dead stock.