DC SHUNT FOR DIGITAL AMMETERS AND MULTIMETER

Install shunt for digital DC current measurement:

Caution: The shunt must be installed in the negative line to avoid damage
to the meter. Positive voltage applied to digital meter terminals #4 and #5
will cause damage to the meter.

An external shunt is supplied with 360 panels that include a DC Digital
Ammeter or Multimeter. Install the shunt at any point in the DC negative
feed line to the panel. Mount it close to the panel to keep the sense wires
that run from the shunt to the meter short. Short sense wires minimize
voltage loss and interference, and result in the most accurate metering.
Mounting it close to the battery bank may make it easier to include more
circuits, such as 24-hour circuits, in the metering. Wire runs greater than 50
feet using #16 AWG wire may produce errors up to 1%. Use 16 AWG wire
for sense connections.

For more information go to www.bluesea.com

TO BATTERY

SWITCH

TO BATTERY

SWITCH

DO NOT

INSTALL SHUNT

IN POSITIVE

FROM NEGATIVE

DC DISTRIBUTION

(ALL LOADS AND

SOURCES)