Wire size – Blue Sea Systems 1408 M-Series Dual Circuit Plus, Main + 3 Position CLB Vertical User Manual

Page 7

Advertising
background image

Segment 2

1.5% voltage drop

eg. battery switch to power distribution panel

Segment 1

1.5% voltage drop

eg. battery bank to battery switch

3% voltage drop along entire circuit path

(from power source to load and return)

Segment 1 + Segment 2 = 3% Voltage Drop

WIRE SIZE

DC Circuits:

Use Blue Sea Systems’ DC Circuit Wizard online at

http://dc.circuitwizard.bluesea.com/ to guide you in suitable wire size

selection for each DC Feed, Main, and Branch Circuit.

Voltage drop along a circuit path is cumulative. To achieve suitable voltage

drop along a path consisting of multiple segments, use the DC Circuit Wizard

to assign voltage drop values to each segment that add up to the desired

voltage drop.
Be sure to measure the length of wire from power source to load and return.

Wire Size (AWG)

Allowable Amperage of Conductors

Outside Engine Spaces

Inside Engine Spaces

16

25.0

21.3

14

35.0

29.8

12

45.0

38.3

10

60.0

51.0

8

80.0

68.0

6

120.0

102.0

4

160.0

136.0

2

210.0

178.5

This ABYC table is for wire with 105°C (122°F) insulation rating and no more

than 2 conductors bundled together. It is not suitable for sizing flexible shore

power cords. The values will allow conductors to reach their full 105°C

(122°F) rated temperature.
Many experts in the marine electrical industry recommend using wires that are

one or two sizes larger than shown in the table above to reduce the operating

temperature of the wire.

5

For more information go to www.bluesea.com

ABYC E-11 Table IV 105°C (122°F) Wire

AC Circuits:

For each AC Feed and Branch circuit, the ABYC table below

lists the minimum wire size.