5.1.4 Modbus TCP

This allows the user to configure the recorder so as to allow it to communicate using Modbus
Transmission Control Protocol.

Figure 2.2.4 Modbus TCP configuration menu

PrefMaster IP

The IP address of the relevant Modbus master. The Preferred master is
guaranteed to be able to connect, even if all slave connections (max. = 4 for TCP)
are in use.

Address

The Modbus address for this slave. This address must be unique for the network to
which it is attached. The recorder will respond to this address and to Address 255.

Input Timeout

Allows a value of between 0 and 3600 seconds to be entered to set the timeout
period for modbus input channels. If a modbus input is not written to within this
period the value of the channel is set to -9999.0 with a 'No Data' status. A value of
0 disables the comms inactivity timeout feature.

Unit ID Enable

Enables/Disables the checking of the Modbus TCP unit identity field.

Strict

The Modbus TCP Unit Identity Field (UIF) does not have to match the

instrument address. The instrument responds only to Hex value FF in
the UIF. iTools finds this instrument only at location 255, and then
stops scanning.

Loose

The Modbus TCP Unit Identity Field (UIF) does not have to match the

instrument address. The instrument responds to any value in the UIF

Instrument The Modbus TCP Unit Identity Field (UIF) must match the instrument

address or no response will be made to messages.

Serial Mode

Slave communications via the side mounted configuration port interface (CPI) clip
(for iTools use.) Parameters: Baud rate 19,200; Parity = none; Number of data bits

PrefMaster IP

Address

Input Timeout

Unit ID Enable

Serial Mode

Time Format

PrefMaster Conn

Network.Modbus

123.123.123.123

1

0 sec

Instrument

Modbus Slave

Seconds

123.123.123.123

Response Time

Master Conn 1

Response Time

Master Conn 2

Response Time

Master Conn 3

Response Time

Master Conn 4

Response Time


0

0.0.0.0

0

0.0.0.0

0

0.0.0.0

0

0.0.0.0

0