Wire burner, Model 301gas burner — instruction manual, General wiring requirements – Carlin 301GAS Inst Manual User Manual

Page 11: Verify power supply, Checking burner flame signal, Code compliance

Advertising
background image

Model 301GAS burner — Instruction manual

Carlin part number MN301GAS Rev. 03/14/11

– 11 –

Where appliance instructions differ from this manual, follow the appliance instructions.

3. Wire burner

General wiring requirements

Read and follow the guidelines below. Failure
to comply could result in severe personal injury,
death or substantial property damage.

Electrical shock hazard — Disconnect electrical
supply to the burner before attempting to service.

Electrically ground burner — The burner must be
grounded in accordance with local codes or, in the
absence of local codes, with the National Electrical
Code, ANSI/NFPA 70, or

CSA C22.1/CSA C22.2

Canadian Electrical Code for Canadian installs

.

Label all wires before removing for servicing. Wiring er-
rors could result in unsafe appliance/burner operation.

Read appliance manufacturer’s instructions com-

pletely before wiring burner.

The 60200FR control requires a constant 120

vac

power source from the appliance as well as power
from the appliance limit circuit. See Figure 11.
Check polarity carefully. If hot and neutral wires are
reversed at appliance power source, the control will
lockout on flame failure.

If replacing any of the wire supplied with the burner,
use minimum #18 AWG 125°C or better.

Figure 11 Wiring diagram — 301GAS burner with 60200FR primary control

Verify power supply

1. The burner requires a 120

vac

/60

hz

/single-phase power supply, with at least a 10-amp

fuse. The current draw will be (when equipped with typical motor and Carlin 41800
electronic ignitor) approximately:


2. The 120

vac

power connections to the black and red/white wires of the 60200FR

must be the same polarity

from the same power source. DO NOT attempt to supply

separate power sources. Check the power from the appliance with a voltmeter. Verify
that the supply to the black and red/white wires are from the 120

vac

HOT side and

that the power is no less than 102

vac

nor more than 132

vac

.

Checking burner flame signal

The 60200FR uses flame rectification to detect the flame. Because the grounded metal
surface area near the flame rod is much larger than the surface of the flame rod, current
flows through the flame more easily in one direction than the other. This causes an AC
voltage applied to the flame rod to result in a DC current. (Note that, if the flame rod should
touch a grounded metal part, the current would be AC, not DC, and the control would not
sense flame causing a flame failure.)
The 60200FR control has a 3 mm flame signal test jack (next to the terminal block) that
can be used with a flame signal meter, such as the Honeywell W136. Or you can use a
standard 3 mm stereo plug fitted with two leads (Carlin part number 99017). Connect these
leads in series with your ammeter leads to read DC microamps.
The minimum flame signal needed to satisfy the 60200FR sensing circuit is 0.8 microamps.
The control will register flame failure at any lower signal.

Black

call for heat 120

from limit circuit

VAC

White

Orange

Blue

Red/White

From appliance 120

power source

for constant power

VAC

From appliance 120

limit circuit to

start burner on call

VAC

Connect to

appliance

neutral entrance

120

VAC

Connect ground per

NEC, CEC or local

constant 120

line

VAC

Violet

Violet

Black/White

A

A

Dry contacts to alarm circuit

(24

or , max load 2

)

V AC

DC

AMPS

60200FR

Burner junction box

Ignitor

Electrode

Green

Brown

Flame rod

Chassis ground

Airflow
switch

Jumper or 24

to thermostat

(anticipator setting 200 mA)

VAC

T

T

30113-R1

Red

Lo gas pr sw

Black/
Yellow

Hi gas pr sw

Flg. Door Switch

Black

Yellow

Yellow

Black

Black

Yellow

Installer

wiring

Wire

nuts

Crimp

connectors

Black/White

White

White

Motor

Gas train junction box

NO

Com

Com

NC

Black/
Yellow

Black

Black

Solenoid valve

Diaphragm valve

White

White

White

Yellow

Black

Black/White

Black/White

Code compliance

The burner/appliance installation must comply with codes listed
on page 2 and any other locally applicable codes.