Prepare site • prepare burner • mount burner – Carlin 301GAS Inst Manual User Manual

Page 9

Advertising
background image

Model 301GAS burner — Instruction manual

Carlin part number MN301GAS Rev. 03/14/11

– 9 –

Where appliance instructions differ from this manual, follow the appliance instructions.

Mount burner in appliance

• Verify appliance burner front plate dimensions and bolt locations.

• Slide gasket supplied with burner over end of air tube.
• Insert burner into appliance opening and bolt in place.
• Level the housing if necessary by loosening the set screws securing the

housing to the air tube. Retighten the set screws.

Inspect components and wiring

• Visually inspect all burner components and wiring.
• Verify that wiring is intact and leads are securely connected.
• Verify that all burner components are in good condition.
• Check gas pressure switch settings. Set the low gas pressure switch at

manifold setting minus 50%. Set the high gas pressure switch at manifold
setting plus 50%.

Figure 8 Gas orifice location

Install gas train on burner

1. The standard burner gas train is shipped fully assembled, with the piping

disconnected at the gas train union. See separate instructions if installing
an optional knocked down gas train.

2. Connect the gas train at the union (Figure 9).

To avoid damage to gas train components, do not hold compo-

nents with a pipe wrench or overtighten. Use only a crescent
wrench or other means. Failure to comply could result in severe
personal injury, death or substantial property damage.

3. Connect the flexible conduit, pre-attached to the primary control J-box, to

the gas train J-box, and attach the wires to the terminal strip inside the
gas train J-box.
a. Match wire colors of the incoming wires to those pre-wired to the terminal

strip inside the gas train J-box.

b. See the label in the burner junction box or the wiring diagram on

page 11.

Gas valve vent opening — The V48 diaphragm gas valve is

fitted with a factory-installed vent liminting orifice in the vent
connection. Do not remove or change the size of this orifice. If
local codes require, install piping from the vent connection to
outside, sized and installed as required by codes.

Figure 9 Gas train installation

Inspect/redrill gas orifice

If the burner is installed, you must disconnect power to burner

and close main manual gas valve before proceeding. Failure to
do so could result in severe personal injury, death or substantial
property damage.

In the state of Massachusetts, when lever-type gas shutoffs are

used, they must be T-handle type only.

1. Turn off power to the burner/appliance before proceeding.
2. Close main manual gas valve in gas supply line to burner.
3. Disconnect the burner gas train union if the burner/gas train is installed.

See Figures 8 and 9.

4. Locate the correct orifice drill size in Table 1, page 7 (or appliance

manual). Then check actual orifice size using that size drill bit.

5.

If the gas orifice is smaller than required, unscrew the orifice nipple
from the elbow. Then redrill the orifice to the correct size. Replace the
gas train, using only pipe dope listed for use with liquefied petroleum
gases.

6.

If the gas orifice is larger than required, remove the orifice nipple
from the elbow. Obtain a replacement orifice nipple. If necessary, drill
the correct orifice hole in the new orifice to the correct size.

7. Replace gas train. Seal pipe joints with a small amount of pipe dope.

Use only pipe dope approved for use with propane gas.

1. Prepare site • prepare burner • mount burner

(continued)

Advertising