MAINTENANCE

25

FAQS

24

Battery Replacement

The OmniGuard Rackmount series has easy-to-replace hot-swappable batteries.
Please read the following warning statements before attempting to service the
battery(s). NOTE: If there is a power interruption while replacing the hot-
swappable batteries, with the UPS on, the load will not be backed up.

Symptom

UPS will not turn on

UPS operates in battery mode
only, even though there is
normal AC present

The UPS emits a sustained tone

The Site Wiring Fault LED is
illuminated

The Battery On LED is
illuminated, but there
is no output

UPS does not provide expected
backup time with internal
batteries or with a battery pack

Replace Battery LED is
illuminated

UPS occasionally emits a beep

Overload LED is illuminated and
a constant alarm sounds

The Battery On LED is blinking
and the audible alarm is silent

Possible Cause

On/Off/Test button not pushed

Input AC circuit breaker is
tripped

UPS has detected an internal
fault

Incorrect service wiring

The UPS is being controlled via
its computer port.

The batteries may be weak or
at the end of useful service life.
The battery pack’s circuit
breaker may be tripped.

Weak or bad batteries/bad
battery connection

Normal operation

The load has exceeded the UPS’
capacity

The UPS is in either the Buck
mode or the Boost mode

What To Do

Press the On button
momentarily (one beep to
start UPS)

Reset circuit breaker by
pressing the plunger back in.
If the AC circuit breaker trips
after UPS starts up, reduce the
load on the UPS.

Call for service

Have a qualified electrician
correct the service wiring

Disconnect the computer cable
from the UPS and press the On
button momentarily. If UPS
works normally, software has
control of the UPS.

Charge the batteries for 8 hours
and retest. If the backup time
is still less than expected, the
batteries may need to be
replaced, even though the
Weak/Bad Battery LED is not
illuminated. Reset the battery
pack’s circuit breaker.

Check battery connection/
replace batteries. Follow battery
replacement procedures in
section 6.

The UPS is performing its
intended function.

Check the specifications (see
section 8). Remove part of the
load.

The UPS is performing its
intended function.

WARNING: This Uninterruptible Power Source contains
potentially hazardous voltages. Do not attempt to disassemble
the unit beyond battery replacement procedures below. Except
for the battery, this UPS contains no user-serviceable parts.
Repairs should be performed by service personnel only

Series Model #

Battery Model #

F6C110-RKM-2U

12V 7.2Ah

F6C150-RKM-2U

12V 4.5Ah

F6C230-RKM-2U

12V 9Ah

F6C320-RKM-3U

12V 12Ah

CAUTION: Do not open or mutilate batteries. Released
electrolyte is harmful to the skin and eyes and may be toxic.

CAUTION: Although battery system voltages are only 24VDC
and 48VDC, the battery system can still present a risk of
electrical shock. The current capability of a battery is sufficient
to burn wire or tools very rapidly, producing molten metal.
Observe these precautions when replacing the batteries:

1. Remove watches, rings, or other metal objects.

2. Use hand tools with insulated handles.

3. Do not lay tools or other metal parts on top of batteries.

CAUTION: Replace batteries with the same number and type as
originally installed in the UPS. These batteries have pressure-
operated vents.