Check Power Installation
Checking main power wiring
WARNING:
Power must be turned OFF when you perform this procedure.
Check resistance between phases, neutral and earth busses.
o
Phase to phase; resistance should be 10M
Ω or higher
o
Phases to earth; resistance should be 10M
Ω or higher
o
Neutral to earth; resistance should be 0
Ω
o
Phase to neutral; resistance should be 10M
Ω or higher
Checking load wiring
Check resistance between the load terminals and the neutral bus:
o
Above 1 M
Ω - Normal when no load is connected
o
Between 1 - 1000
Ω - Normal when loads are connected
o
Below 1
Ω - Indicates a dead short in the load wiring
WARNING:
A dead short can cause dimmer module damage.