Load connections, Earth/ground connections, Neutral connections – ETC SmartPack CE Wall Mount User Manual
Page 13: Earth/ground connections neutral connections, 16awg and 6mm, Incoming load wiring earth/ground bus

Installation Procedure
11
Load Connections
Earth/Ground Connections
Connect the earth/ground conductor for each load to the Earth/Ground Bus.
Neutral Connections
Step 1:
Prepare load conductors by stripping 6mm of insulation from the end.
Step 2:
Insert the stripped end into the terminal and tighten the screw using a 4.75mm
(3/16”) wide slotted style screwdriver.
•
Terminals accept wire between 1.5mm
2
/ 16AWG and 6mm
2
/ 8AWG.
•
Take care not to tighten the load connection onto the wire insulation.