Notes:
1) Fastener assembly spacing for perimeter sheets is the same as

required for the fastener spacing of the roof field area sheets.

*Installation of 12’ wide membrane requires 2 rows of

perimeter sheets fastened 12” o.c.

**Gypsum or Cementitious Wood Fiber Decks in the 100 to 129

mph wind zone require installing 3 rows of perimeter sheets.

Notes:
1) When Lightweight Insulating Concrete Decks are installed

over a Steel Deck, the fasteners must penetrate through the
Lightweight Insulating Concrete Deck, and must attach to
the Steel Deck.

2) Cementitious Wood Fiber, Gypsum, and Wood Decks are not

acceptable for a mechanically attached roof system installation
in the

* 130 mph wind zone.

* XHD Flex Plates and Fasteners 6” o.c. SXHD Flex Plates and

Fasteners 12” o.c.