Please read and save these instructions. Read carefully before attempting to assemble, install, operate or maintain the product described. Protect yourself and others by observing all
safety information. Failure to comply with instructions could result in personal injury and/or property damage! Retain instructions for future reference.

FW1101

0711

Supersedes

1008

1. LOCATION

Indoor Use Only

2. WIRE ROUTING

3. GROUNDING

IL0737

4”

Min.

4”

Min.

4”

Min.

4”

Min.

IL0738

IL0739

MOTOR

IL0740

IL0741

IL0742

IL0743

IL0744

Mount the Artesian Drive
unit as close as possible
to the service entrance
panel.

Use a dedicated branch circuit for the Artesian
Drive. Wire directly from the service entrance
panel.

Use the holes and
guides provided

Allow a 4”
clearance around
the Artesian
Drive box for
cooling

Mount unit to a sturdy
supporting structure (wall or
post)

DO NOT drill
holes in the
Artesian Drive
box

DO NOT wire to a sub panel
located in a home.

It is preferable to wire directly to
the service entrance panel.

When possible, DO NOT run
Artesian Drive input power or
motor wires in parallel with
house wiring.

Avoid runing out-building wires
in parallel with motor wires.

Keep input power and motor
wiring separated by at least 8”.

Input power

Motor

DO NOT run input power and
motor wires together.

Keep separated by at least 8”

If it is necessary to run wiring in paralell, keep
Artesian Drive input power and motor wires at least
8” from other house wiring.

Cross over other branch
circuits and house wiring
at 90º

Insure that a
proper utility
ground rod is
present and
connected.

A dedicated ouput ground
wire from the Artesian
Drive must be connected
to the motor (motor wires
and ground wires must be
bundled together).

An input power ground wire from the supply panel
must be connected to the Artesian Drive.

Use the service
entrance panel
ground ONLY

DO NOT run

ground wire separate.

Motor ground wire MUST be
bundled with motor wires.

Avoid multiple ground paths

Service Entrance
Panel

Service Entrance
Panel

Service Entrance
Panel

Service Entrance
Panel

Service Entrance
Panel

Service Entrance
Panel

Service
Entrance Panel

IN HOME

Sub Panel

GND

GND

GND

Motor

GND

GND

Motor

Pump

GND

GND

GND

GND

Service

Entrance Panel

Branch 3

Branch 2

Branch 1

8” Min.

8” Min.

Telephone

Motor

8” Min.

Satellite /

Antenna

Wire

GND

GND

8” Min.

OK

8” Min.

90º

GND

GND

GND

8” Min.

GND.

GND.

Motor

Pump

GND.

GND.

Motor

Pump

GND.

GND.

GND.

GND.

GND.

Motor

Pump

022688

Insure that a proper utility ground
rod is present and connected.

IL0783

Motor

Power to
Motor

Power Supply from Circuit
Breaker

Inlet

Outlet

Inlet

Outlet

Inlet

Outlet

Inlet

Outlet

Inlet