JULABO FLW4006 Recirculating Coolers User Manual

Page 12

Advertising
background image

12


Recirculating Cooler
Cooling

FL4006 FLW4006
air cooled

water cooled

Working temperature range

°C

-20 ... +40

-20 ... +40

Temperature stability

°C

±0.5

Temperature selection:

digital

via key pad

indication

on

LED-DISPLAY

remote control via personal computer

indication on monitor

Temperature indication:

LED-DISPLAY

Resolution

°C 0.1

Temperature control

PID

1

Temperature sensor

Pt 100

Excess temperature protection

85 °C - fixed value

Low liquid level protection

float switch

Cooling capacity
Medium: Mixture water-glycol

°C
kW

+20 0 -10

+20 0 -10

4.0 1.9 0.9

4.0 1.7 0.7

Cooling compressor

1- stage

Refrigerant

R404A

Electrical connections:

Computer

interface

RS232

Alarm

output

for external alarm signal

Circulating pump:

discharge, max.

at 0 bar

l/min

60

60

pressure, max.

at 0 liter

bar

0.5 ... 6.0

0.5 ... 6.0

pressure, adjustable at 0 Liter

Feed pressure indication

bar

Manometer Manometer

Filling level indicator

sight glass

Filling volume

from ... to

liters

24 ... 30

Dimensions (WxLxH)

cm

60x76x115

Weight

kg

157

160

Ambient temperature range

°C

5 ... 40

Return flow temperature

°C

80

max.

Cooling water

Flow rate at 20 °C inlet temperature


l/min


-----

6.6

IP class according to IEC 60 529

IP

21

Mains power connection

400 V/3PNPE/50 Hz

V/ Hz

360-440/3PNPE/50

360-440/3PNPE/50

Current draw at 230 V

A

12

13

Mains power connection

230 V/3PPE/60 Hz

V/ Hz

207-253/3PPE/60 207-253/3PPE/60

Current draw at 208V / 220 V

A

16

------


All measurements have been carried out at: rated voltage and frequency,
ambient temperature: 20 °C

Advertising