3 case and ambient conditions, 4 approval/approval marks, Approval/approval marks – JUMO 705040 mTRON T - Router Module Installation Instructions User Manual
Page 32: 4 appendix

4 Appendix
32
4.1.3
Case and ambient conditions
4.1.4
Approval/approval marks
Case type
Plastic case for DIN rail mounting in the control cabinet (indoor use);
DIN rail acc. to DIN EN 60715, 35 mm x 7.5 mm x 1 mm
Dimensions (W x H x D)
22.5 mm x 103.6 mm x 101.5 mm (without connection elements)
Weight
Approx. 125 g
Protection type
IP20, acc. to DIN EN 60529
Ambient temperature range
-20 to +55 °C
Storage temperature range
-40 to +70 °C
Resistance to climatic conditions
Relative humidity
≤
90 % annual average without condensation (cli-
matic class 3K3 acc. to DIN EN 60721-3-3 with extended tempera-
ture and humidity range)
Site altitude
Up to 2000 m above sea level
Mechanical ambient conditions
1
Classification acc. to DIN EN 60721-3-3, table 6, class 3M2
1
Test conditions are listed in the System Descripton B 705000.8.
Approval mark
Testing agency
Certificate/certifica-
tion number
Inspection basis
Valid for
c UL us
Underwriters Laborato-
ries
E201387
UL 61010-1 (3. Ed.),
CAN/CSA-22.2
No. 61010-1 (3. Ed.)
all types