Technical data, Analog inputs – JUMO 705020 mTRON T - Analog Input Module, 4-Ch. Data Sheet User Manual

Page 3

Advertising
background image

JUMO GmbH & Co. KG
Delivery address: Mackenrodtstraße 14

36039 Fulda, Germany

Postal address:

36035 Fulda, Germany

Phone:

+49 661 6003-0

Fax:

+49 661 6003-607

E-mail:

[email protected]

Internet:

www.jumo.net

JUMO Instrument Co. Ltd.
JUMO House
Temple Bank, Riverway
Harlow, Essex CM20 2DY, UK
Phone: +44 1279 635533
Fax:

+44 1279 635262

E-mail:

[email protected]

Internet: www.jumo.co.uk

JUMO Process Control, Inc.
6733 Myers Road
East Syracuse, NY 13057, USA
Phone: 315-437-5866

1-800-554-5866

Fax:

315-437-5860

E-mail:

[email protected]

Internet: www.jumousa.com

2013-05-07/00529109

Data Sheet 705020

Page 3/10

Technical data

Analog inputs

General information

Thermocouples

RTD temperature probe

Number 4

A/D converter

Dynamic resolution up to 16 bit

Designation

Standard

Measuring range

Measuring accuracy

a

a

The accuracy values refer to the maximum measuring range. Smaller measuring ranges lead to reduced linearization accuracy.

Ambient
temperature influence

Fe-CuNi “L”

-200 to +900 °C

 0.1 % from -100 °C

300 ppm/K

Fe-CuNi “J”

DIN EN 60584

-200 to +1200°C

 0.1 % from -100 °C

300 ppm/K

Cu-CuNi “U”

-200 to +600 °C

 0.1 % from -130 °C

300 ppm/K

Cu-CuNi “T”

DIN EN 60584

-200 to +400 °C

 0.1 % from -150 °C

300 ppm/K

NiCr-Ni “K”

DIN EN 60584

-200 to +1372 °C

 0.1 % from -80 °C

300 ppm/K

NiCr-CuNi „E“

DIN EN 60584

-200 to +1000 °C

 0.1 % from -80 °C

300 ppm/K

NiCrSi-NiSi “N”

DIN EN 60584

-100 to +1300 °C

 0.1 % from -80 °C

300 ppm/K

Pt10Rh-Pt “S”

DIN EN 60584

-50 to 1768 °C

 0.15 % from 20 °C

300 ppm/K

Pt13Rh-Pt “R”

DIN EN 60584

-50 to 1768 °C

 0.15 % from 20 °C

300 ppm/K

Pt30Rh-Pt6Rh “B”

DIN EN 60584

0 to 1820 °C

 0.15 % from 400 °C

300 ppm/K

W5Re-W26Re „C“

0 to 2320 °C

 0.15 % from 500 °C

300 ppm/K

W3Re-W25Re “D”

0 to 2495 °C

 0.15 % from 500 °C

300 ppm/K

W3Re-W26Re

0 to 2400 °C

 0.15 % from 500 °C

300 ppm/K

Chromel-Copel

GOST 8.585-2001

-200 to +800 °C

 0.15 % from -80 °C

300 ppm/K

Chromel-Alumel GOST

8.585-2001

-200 to +1372 °C

 0.10 % from -80 °C

300 ppm/K

PLII (Platinel II)

0 to 1395 °C

 0.10 % from -80 °C

300 ppm/K

Linear

0 to 75 mV

 0.1 %

300 ppm/K

Cold junction

Pt100 internal

Cold junction accuracy

 1 K

Designation

Standard

Measuring range

Measuring accuracy

a

Ambient
temperature influence

Pt100

DIN EN 60751

-200 to +850 °C

50 ppm/K

2-wire circuit

 0.15 %

3-wire/4-wire circuit

 0.05 %

Pt500

DIN EN 60751

-200 to +850 °C

50 ppm/K

2-wire circuit

 0.30 %

3-wire/4-wire circuit

 0.15 %

Pt1000

DIN EN 60751

-200 to +850 °C

50 ppm/K

2-wire circuit

 0.20 %

3-wire/4-wire circuit

 0.08 %

Ni 100

DIN 43760

-60 to +250 °C

50 ppm/K

2-wire circuit

 0.36 %

3-wire/4-wire circuit

 0.24 %

Pt100

JIS 1604

-200 to +650 °C

50 ppm/K

2-wire circuit

 0.20 %

3-wire/4-wire circuit

 0.06 %

Advertising