6 instrument description – JUMO 605041 Explosion-protected surface-mounting thermostat, ATH-EX Operating Manual User Manual
Page 19

19
6 Instrument description
Capillary
and
probe material
Min. bending
radius of
capillary
5 mm
Switching point
accuracy
in % of scale span, referred to limit at T
a
+22°C.
Mean ambient
temperature
effect
in % of scale span, referred to limit.
A deviation of the ambient temperature at the housing and / or the capillary
from the calibrated ambient temperature +22°C will result in a switching point
displacement:
higher ambient temperature = lower switching point
lower ambient temperature = higher switching point
End of scale
Capillary
Probe
up to +200°C
copper, Mat. Ref. 2.0090
electrotinned 1.5 mm dia.
copper, Mat. Ref. 2.0090
electrotinned brazed
up to +300°C
copper, Mat. Ref. 2.0090
electrotinned 1.5 mm dia.
stainless steel,
Mat. Ref. 1.4571 brazed
up to +500°C
stainless steel,
Mat. Ref. 1.4571
1.5 mm dia.
stainless steel,
Mat. Ref. 1.4571 welded
up to +300°C
stainless steel,
Mat. Ref. 1.4571
1.5 mm dia.
stainless steel,
Mat. Ref. 1.4571 welded
TW
in upper third of scale
+0
%
-4
at scale start
+0
%
-6
STW
in upper third of scale
+0
%
-5
at scale start
+0
%
-7
Surface-mounting thermostats with end of scale
< +200°C
≥ +200°C ≤ +350°C
> 350°C
TW
STW
TW
STW
TW
STW
on thermostat head %/°C
0.08
0.17
0.06
0.13
0.14
0.12
on capillary %/°C per meter
0.047
0.054
0.09
0.11
0.04
0.03