Valid range valid range, Allo, Alhi hys1 hys2 – JUMO 14597 safetyM TB/TW08 Temperature Limiter and Temperature Monitor Data Sheet User Manual
Page 4

2012-07-01/00524703
Data sheet 70.1170
JUMO GmbH & Co. KG • 36035 Fulda, Germany
Page 4/10
Switching behavior, direct
Switching behavior with differential value calculation with prefix (ex-factory)
Pre alarm range
Alarm range
valid range
Relay output KV
LED KV lights up yellow
active
Relay output KV inaktive
LED KV off
ALLO
Relay inaktive
LED K1 lights up red
Relay K1 aktive
Limit Value
AL
Measured Value
LED OK
green
lights up
Pre alarm
ALHI
Hys1
Hys2
S
P
Ö
3,15A
5
7
6
S
P
5
7
6
Ö
3,15A
Measured Value
-200°C
300°C
AL = 150°C (inverse)
0°C
200°C
100°C
-100°C
300°C
200°C
100°C
0°C
-100°C
-200°C
ALD = 50°C
IN2
INP
valid
range
valid
range
Hys1
Hys1
All difference values diF = INP-IN2 are shown in the picture.
Inside the valid range (green) all values are smaller than the
setting for the difference ALd = 50.
INP = 101°C, IN2 = 50°C
101 - 50 = 51 exceeds Ald = 50 and lies out of the valid range.
INP = 50°C, IN2 = 50°C
50 - 50 = 0 and lies inside the valid range.
Example 1:
Example 2:
The area between the dot and dash lines indicate
the span of the hysteresis (factory setting: 1K)
he inputs INP and IN2 are additionally monitored
in regards to the limit value AL=150°C
T
50°C
1
2