JUMO 14597 safetyM STB/STW Ex - Safety Temperature Limiter and Safety Temperature Monitor Data Sheet User Manual

Stb/stw ex, Dgrl, Brief description

Advertising
background image

JUMO GmbH & Co. KG
Delivery address: Mackenrodtstraße 14

36039 Fulda, Germany

Postal address:

36035 Fulda, Germany

Phone:

+49 661 6003-0

Fax:

+49 661 6003-607

E-mail:

[email protected]

Internet:

www.jumo.net

JUMO Instrument Co. Ltd.
JUMO House
Temple Bank, Riverway
Harlow, Essex CM20 2DY, UK
Phone: +44 1279 635533
Fax:

+44 1279 635262

E-mail:

[email protected]

Internet: www.jumo.co.uk

JUMO Process Control, Inc.
6733 Myers Road
East Syracuse, NY 13057, USA
Phone: 315-437-5866

1-800-554-5866

Fax:

315-437-5860

E-mail:

[email protected]

Internet: www.jumousa.com

Page 1/16

2012-10-01/00542385

JUMO safetyM STB/STW Ex
Safety Temperature Limiter and
Safety Temperature Monitor According
to DIN EN 14597

Brief description

The compact and freely configurable JUMO safetyM STB/STW Ex can now also enable early
and reliable detection of risks in Ex-areas which could potentially result in personal injuries, en-
vironmental damage, or destruction of the production plant and production materials.
The devices are marked as follows:

The primary task of safety temperature limiters is to reliably monitor thermal processes and to
switch plants to a safe operational state in the event of malfunctions. Along with the existing ap-
provals according to DIN 14597, SIL3, PL e (Performance Level), GL, the device also has ap-
proval according to ATEX and can therefore also be used in Ex-areas. The inputs are intrinsically
safe [Ex ia] so that relevant probes can be connected directly.
Barriers are no longer required. The device is also certified according to DIN EN 50495 and DIN
EN 13463-6 as a monitoring device for potential ignition sources (iPL 2) as specified in the ATEX
directive and can be used to monitor potentially explosive atmospheres containing gas or dust.
The device concept also meets the stringent requirements of DIN EN 61508 and DIN EN 13849.
The 1oo2D structure ensures reliable detection of faults, meaning that the device concept can
also be used for applications subject to the new Machinery Directive 2006/42/EC.
Along with the keypad, the clear and well structured back-lit display with plain text provides
quick and straight-forward configuration directly on the device. The clear menu structure en-
sures easy operation, which in turn shortens commissioning time. All safety-relevant process
values are displayed and the most important functions are represented by simple icons.

1-sensor variant

2-sensor variant

II (1) (2) (3) G (b1) [Ex ia Ga] [e pz] IIC

II (1) (1) (2) G (b2) [Ex ia Ga] [e py] IIC

II (1) (2) (3) D (b1) [Ex ia Da] [p Dc] IIIC

II (1) (1) (2) D (b2) [Ex ia Da] [p Db] IIIC

Block diagram

1 binary input
for floating contact

1 analog output
standard signal

Voltage supply

AC 110 to 240 V +10/-15 %, 48 to 63 Hz
AC/DC 20 to 30 V, 48 to 63 Hz

USB Interface
for setup program

1 relay Output Alarm
SPDT (changeover contact)
with fuse cut-out

1 relay output pre-alarm KV)

(

SPDT (changeover contact)

LCD display
with white background lighting

4 keys
for operation and
acknowledgement of alarms

Mesured Value

Universal analog Input 1

Universal analog Input 2

701155

STB/STW Ex

mit 1oo2D -Struktur

Data Sheet 701155

Type 701155/ ...¶

Special features

k 1oo2D structure for high degree of process

reliability

k LCD display with background lighting

and plain text display for more simplified
operation

k Setup program for configuration and

archiving via USB interface

k Digital input filter with adjustable

filter time constant

k Pre-alarm absolute or adjustable as a mar-

gin from the limit value

k Wide voltage supply range from AC 110

to 240 V +10 % /-15 % or
AC/DC 20 to 30 V

k Can be configured as safety temperature

limiter (STB) or safety temperature monitor
(STW)

k 12 linearizations can be set

k Internal and external unlocking possible

k Approvals for DIN EN 14597, SIL, PL e

(Performance Level e),

k Approval GL submitted

Approvals/approval marks

(see "Technical data")

DGRL