6 technical data – JUMO 902815 Dtrans T100 Screw-In RTD Temperature Probe Without/With Transmitter Operating Manual User Manual
Page 20

20
6 Technical data
Overrange
Linear rise up to 20.5 mA
(according to
NAMUR recommendation 43)
Probe short-circuit/
probe or lead break
≤
3.6 mA or
≥
21.0 mA (configurable)
Current limiting
on probe short-circuit
or probe break
≤
25 mA
Output
Output signal
Proportional DC current
4 to 20 mA, 20 to 4 mA
Transfer characteristic
Linear with temperature
Maximum burden (R
B
)
R
B
= (U
b
- 8 V) devided by 23 mA,
max. 600
Ω
Burden error
≤
±0.02 % per 100
Ω
The % value refers to the range end value
20 mA
Settling time on a
temperature change
≤
5 s
Settling time after a
switch-on or reset
≤
5 s
Measuring accuracy
of electronics
0.1 °C or 0.08 %
The % value refers to the measuring span
that was set, the larger value applies
Electrical data
Voltage supply
(U
b
)
DC 8 to 35 V (pin 1 = +, pin 3 = -),
operation solely with SELV or PELV-
transmitter supply
(according to DIN EN 61140)
Protection rating
III (according to DIN 61140)