6electrical installation – Lenze E94AYCCA User Manual

Page 42

Advertising
background image

6

Electrical installation

Wiring the CAN bus

EDK94AYCCA DE/EN/FR/ES/IT 3.0

42

l

H1_E_INST−Leitungslaenge 3−9400

Check repeater application

Given:

l

Baud rate:

125 kbit/s

l

Cable cross−section:

0.5 mm

2

l

Number of nodes:

28

l

Cable length:

450 m

Test sequence

Cable length

See

1. Total cable length at 125 kbit/s:

630 m

Tab. 1

2. Segment cable length for 28 nodes and a cable cross−section

of 0.5 mm

2

:

360 m

Tab. 2

3. Comparison: The value under point 2 is smaller than the required cable length of 450 m.

Conclusion

l

It is not possible to use a cable length of 450 m without installing a repeater.

l

After 360 m (point 2) a repeater must be installed.

Result

l

The Lenze repeater, type 2176 (cable reduction: 30 m), is used.

l

Calculation of the max. cable length:
First segment: 360 m
Second segment: 360 m (according to Tab. 1) minus 30 m (cable reduction when a repeater is

used)

à Max. possible cable length with repeater: 690 m.

à Now the required cable length is possible.

)

Note!

The use of a further repeater is recommended as a

ƒ