Electrical installation

Ethernet POWERLINK connection

6

EDK94AYCEP DE/EN/FR/ES/IT 4.0

39

l

H2_EthernetAnschluss−Ethernet_KabelSpezifikation

Ethernet POWERLINK connection

You can use a standard Ethernet patch cable for connection to the communication module
(see "Ethernet cable specifications" (

^ 41)).

Mounting and dismounting of the Ethernet cables has been optimised for the use of
connectors according to the "Automation Initiative of German Domestic Automobile
Manufacturers" (AIDA).

)

Note!

Plug/remove the Ethernet cable plug vertically into/from the socket to make
sure that the RJ45 socket will not be damaged.

ƒ The Ethernet POWERLINK connection is made via RJ45 sockets X211 and X212.
ƒ Do not wire, if possible, more than 10 nodes in succession in a network line.
ƒ In case of more than 10 nodes you should deactivate the automatic calculation of the

hub level in the »Engineer« and enter it manually to increase the performance.

ƒ At a cycle time of 1 ms, approx. 25 mandatory nodes can be operated.

– The number of nodes can be increased if the EPL cycle time is increased as well.