Commissioning

Before switching on

7

EDK94AYCEP DE/EN/FR/ES/IT 4.0

43

l

H1inbet−Teilnehmeradresse_E94AYCEP

7

Commissioning

Before switching on

(

Stop!

Before switching on the standard device with the communication module for
the first time, check the entire wiring for completeness, short circuit and earth
fault.

Setting the node address

E94YCEP001D

ƒ In case of several interconnected Ethernet POWERLINK nodes, the addresses must

differ from each other.

ƒ For each device, the node address at the DIP switches 1 ... 128 and in code C13044 /

C14044must be set identically.

ƒ Valid node address in the Ethernet POWERLINK network:

Node address

Meaning

240

E94AYCEP is a managing node.

1 … 100

E94AYCEP is a controlled node with another E94AYCEP as managing node.

1 … 239

E94AYCEP is a controlled node with a managing node of a different
manufacturer.

ƒ Lenze setting of the DIP switches 1 ... 128 = OFF (invalid value "0")
ƒ The housing labelling corresponds to the valencies of the individual DIP switches for

determining the station address.