Wiring, 4electrical installation – Lenze E82ZAFLC010 User Manual
Page 36
Advertising

Electrical installation
Wiring
EDK82ZAFLC−010 DE/EN/FR 4.0
36
l
H1_E_INST−INS_Klembesch
Wiring
Basic structure of a LECOM−B network
3
3
3
S
S
S
1
2
2
2
0 m
1000 m
E82ZAFL005
No.
Element
Comment
1
Master computer
E.g. PC or PLC with RS485 master interface module
2
Bus cable
Max. length: 1000 m
3
LECOM−B slave
Standard device applicable with E82ZAFLC0xx function
module
Specification of the transmission cable
Specification of transmission cable for RS485
l
Total cable length up to 300 m:
Cable type
LIYCY 1 x 2 x 0.5 mm
2
shielded
Cable resistance
£ 40 W/km
Capacitance per unit length
£ 130 nF/km
l
Total cable length up to 1200 m:
Cable type
CYPIMF 1 x 2 x 0.5 mm
2
shielded
Cable resistance
£ 40 W/km
Capacitance per unit length
£ 130 nF/km